APPLICATIONS

These cables are used indoor fire alarm systems that transmits the signal and data between conrtol panels , dedectors , buttons and area control modules.

CABLE CONSTRUCTION  
Conductor Stranded Copper Wire Class 5
Insulation Ceramicized Silicon
Insulation Color DIN 47100 Color Coded
Stranding Twisting in Layers
Separator Tape Pes Tape
Flame Barrier Fiberglass Tape
Screen Al-Pes Tape + Earth Wire
Outer Sheath HFFR Orange
Product Types LIH(St)H FE180 PH120
Packing 500 – 1000 meters
ELECTRICAL PARAMETERS  
Working Temperature – 30 ºC + 70 ºC
Bending Radius (min.) 10 x D
Working Voltage 300 / 500 V
Insulation Resistance >200 MΩxkm
Conductor Resistance 0.22 mm² : 96 Ω / km – 0.50 mm² : 39 Ω / km
0.75 mm² : 26 Ω / km – 1.00 mm² : 19.50 Ω / km
1.50 mm² : 13.30 Ω / km – 2.50 mm² : 7.98 Ω / km
Test Voltage 0.22 mm² : 1200 V – 0.50 mm² : 1200 V
0.75 mm² : 1200 V – 1.00 mm² : 1200 V
1.50 mm² : 2500 V – 2.50 mm² : 2500 V