APPLICATIONS

These cables are used for transmission of analoge and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroluem plants, etc… . Instrumentation cables are not allowed for direct connection to a low impedance sources, e.g. public mains electricity supply. These cables are not recommended for direct burial. They are for indoor and oudoor installation, in dry and wet locations; on racks, trays, in conduits.

CABLE CONSTRUCTION
ConductorPlain Annealed Copper Wire
InsulationPe Compound, Bs 6234 Type03
Core identificationBlack / Blue ; With Numbered Tape Under Separator Tape Of The Pair Screen
PairTwo Conductors Twisted To A Pair
PIMF ConstructionPolyester Tape Above The Pair, Al-Pes Tape Over Tinned Copper Drain Wire, 0,50 mm²
StrandingPIMF Laid Up In Layers Of Optimum Pitch
SeperatorPes Tape
ScreenAl-Pes Tape Over Tinned Copper Drain Wire 0,50 mm²
Outer SheathPvc Comp., Flame Retardant; Tm1, Bs 7655
General FeaturesUV, Chemical and Oil Resistant
ELECTRICAL PARAMETERS
Working Temperature-40ºC + 70ºC
Bending Radius ( min.)6 x D
Working Voltage300 / 500 V
Insulation ResistanceMin. 5000 MΩxkm
Conductor Resistance0,50mm² : 36,8 Ω/km 1,0mm² : 18,4 Ω/km 0,50mm² : 39,7 Ω/km 1,5mm² : 12,3 Ω/km
Test VoltageUrms core-core : 1000 V Urms core-screen : 1000 V
Insulation Thickness0,50mm² : 0,50mm 1,0mm² : 0,60mm 0,50mm² : 0,60mm 1,50mm² : 0,60mm
Conductor Class, BS 63600,50mm² : Class 1 or Class 5 1,0mm² : Class 1 or Class 5 0,50mm² : Class 5 1,5mm² : Class 2 or Class 5
Mutual Capacitance0,50 mm² : max. 115 pF/m 1,0 mm² : max. 115 pF/m 1,5 mm² : max. 120 pF/m
Capacitance Unbalance (1 kHz) : max. 250 pF/250 m