APPLICATIONS
These cables are used indoor fire alarm systems that transmits the signal and data between conrtol panels , dedectors , buttons and area control modules.
These cables are used indoor fire alarm systems that transmits the signal and data between conrtol panels , dedectors , buttons and area control modules.
CABLE CONSTRUCTION | |
---|---|
Conductor | Electrolytic Copper Wire |
Insulation | Ceramifiable |
Insulation Colours | TS 13767 Colour Code |
Stranding | Pairs Twisted In Layers |
Flame Barrier | Pes Tape + Glass Fiber |
Screen | Drain Wire – AL-PES Band %100 |
Outer Sheath | HFFR Orange |
Product Types | JE-H(St)H…Bd FE 180 PH 120 |
Packing | 500 – 1000 mt |
ELECTRICAL PARAMETERS | |
---|---|
Working Temperature | – 30 ºC + 70 ºC |
Bending Radius ( min.) | 10 x D |
Working Voltage | 225 V |
Insulation Resistance | >100 MΩxkm |
Conductor Loop Resistance | 0,60 mm : 130 Ω / km 0,80 mm : 73,2 Ω / km 1,00 mm : 44,4 Ω / km 1,50 mm² : 24,2 Ω / km |
Test Voltage | 800 V |
Capacity | 120 nF / km |
Capacity Imbalance | 200 pF / 100 m |