APPLICATIONS

These cables are flexible power cables used in marinas and shipyards for power connections to electrical tools and equipment, agricultural machinery, and marine vessels. Due to their structure, they are suitable for use in cold storage and heating systems where there is no risk of contact with hot components. The polyurethane outer sheath is durable and flexible, resistant to moderate mechanical stress, tearing, abrasion, oil, wet environments, and UV exposure.

CABLE CONSTRUCTION  
Conductor Stranded Copper Wire Class 5
Insulation EPR
Insulation Color HD 308-S2
Stranding Twisting in Layers
Outer Sheath PUR Orange
ELECTRICAL PARAMETERS  
Working Temperature -40 ºC to +90 ºC
Bending Radius (min.) 12 x D
Short Circuit Temperature 250°C
Insulation Resistance >200 m Ω x km
Working Voltage 450 / 750 V
CONDUCTOR RESISTANCE  
0.22 mm²: 96 Ω / km 0.50 mm²: 39 Ω / km
0.75 mm²: 26 Ω / km 1.00 mm²: 19.50 Ω / km
1.50 mm²: 13.30 Ω / km 2.50 mm²: 7.98 Ω / km
4.00 mm²: 4.95 Ω / km 6.00 mm²: 3.30 Ω / km
TEST VOLTAGE  
0.22 mm²: 1200 V 0.50 mm²: 1200 V
0.75 mm²: 1200 V 1.00 mm²: 1200 V
1.50 mm²: 2500 V 2.50 mm²: 2500 V
4.00 mm²: 2500 V 6.00 mm²: 2500 V
Cross-section (mm²) Nominal Overall Diameter 

(mm)

Approximate weight

 (kg / km)

Min. Bending Radius (free movement) (mm) Max. Resistance of Conductors at 20°C (ohm / km)
2×1 7.60 66 30 19.50
2×1.5 8.30 82 33 13.30
2×2.5 9.40 113 38 7.98
2×4 11.00 164 44 4.95
2×6 12.20 215 40 3.30
2×10 17.00 399 32 1.91
2×16 18.60 532 23 1.21
3×1 8.10 80 32 19.50
3×1.5 8.70 97 35 13.30
3×2.5 10.00 139 40 7.98
3×4 11.70 203 47 4.95
3×6 13.20 276 44 3.30
3×10 18.30 504 35 1.91
3×16 20.10 688 24 1.21
4×1 9,10 102 36 19.50
4×1.5 9.80 124 39 13.30
4×2.5 11.20 178 45 7.98
4×4 13.10 260 65 4.95
4×6 14.70 353 49 3.30
4×10 20,20 636 39 1.91
4×16 22.10 869 27 1.21
5×1 10,10 122 40 19.50
5×1.5 11.00 149 44 13.30
5×2.5 12.40 215 99 7.98
5×4 14.50 315 72 4.95
5×6 16.30 430 54 3.30
5×10 22.30 769 43 1.91
5×16 24.60 1064 30 1.21
FLAME RETARDANT TEST
IEC 60332-1-2
VDE 0482-332-1-2
EN 60332-1-2
 
SMOKE DENSITY TEST
IEC 61034-2
VDE 0482-1034-2
EN 61034-2
 
CORROSIVE GAS TEST
IEC 60754-2
VDE 0482-754-2
EN 60754-2