APPLICATIONS
These cables are used indoor fire alarm systems that transmits the signal and data between conrtol panels , dedectors , buttons and area control modules.
These cables are used indoor fire alarm systems that transmits the signal and data between conrtol panels , dedectors , buttons and area control modules.
CABLE CONSTRUCTION | |
---|---|
Conductor | Stranded Copper Wire Class 5 |
Insulation | Ceramifiable |
Insulation Colours | DIN 47100 Colors Code |
Stranding | Cores Twisted In Layers |
Seperator | Pes Tape |
Flame Barrier | Glass Fiber Tape |
Screen | Tinned Copper Wire Braiding |
Outer Sheath | HFFR Orange |
Product Types | LIHCH FE180 PH120 |
Packing | 500 – 1000 mt |
ELECTRICAL PARAMETERS | |
---|---|
Working Temperature | – 30 ºC + 70 ºC |
Bending Radius ( min.) | 10 x D |
Working Voltage | 300 / 500 V |
Insulation Resistance | >200 MΩxkm |
Conductor Resistance | 0,22 mm² : 96 Ω / km – 0,50 mm² : 39 Ω / km – 0,75 mm² : 26 Ω / km – 1,00 mm² : 19,50 Ω / km – 1,50 mm² : 13,30 Ω / km 2,50 mm² : 7,98 Ω / km |