HARMONISED CABLES SYMBOLS
HARMONISED CABLES |
---|
REGULATION DESIGNATION |
---|
H | Harmonised regulation |
A | Approved national design |
RATED VOLTAGE |
---|
01 | 100/100 V |
03 | 300/300 V |
05 | 300/500 V |
07 | 450/750 V |
11 | 600/1000 V |
INSULATION MATERIAL |
---|
V | Polyvinlychloride (PVC) |
V2 | PVC, up to +90 °C |
V3 | PVC, for low temperatures |
B | Ethylenepropylene (EPR) |
E | Polyethylene |
X | XLPE PE (cross-linked PE) |
R | Rubber |
S | Silicone Rubber |
SHEATH OR BRAIDING MATERIALS |
---|
V | Polyvinlychloride (PVC) |
V2 | PVC, up to +90 °C |
V3 | PVC, for low temperatures |
V5 | PVC, oil resistance |
R | Rubber |
N | Cloroprene Rubber |
Q | Polyurethane |
C4 | Screen of copper wire braiding |
J | Glass fibre baiding |
T | Testile braiding |
SPECIAL CONSTRUCTION FEATURES |
---|
H | Flat divisible cables |
H2 | Flat non-divisible cables |
H6 | Flat non-divisible cables, for elevators |
H8 | Spiral cables |
CONDUCTOR TYPE |
---|
U | Single-wire round conductor |
R | Multiple-wire round conductor |
K | Fine stranted (for cables for fixed installations) |
F | Fine strands (for flexible cables) |
H | Extra fine strands |
D | Fine stranded for welding cables |
E | Extra fine strands for wilding cables |
PROTECTIVE EARTHING CONDUCTOR |
---|
X | Without protective earthing conductor |
G | With protective earthing conductor |