APPLICATIONS

These cables are used indoor fire alarm systems that transmits the signal and data between conrtol panels , dedectors , buttons and area control modules.

CABLE CONSTRUCTION  
Conductor Stranded Copper Wire Class 5
Insulation Ceramicized Silicon
Insulation Color DIN 47100 Color Coded
Stranding Twisting in Layers
Separator Tape Pes Tape
Flame Barrier Fiberglass Tape
Outer Sheath HFFR Orange
Product Types LIHH FE180 PH120
Packing 500 – 1000 meters
ELECTRICAL PARAMETERS  
Working Temperature – 30 ºC + 70 ºC
Bending Radius (min.) 10 x D
Working Voltage 300 / 500 V
Insulation Resistance >200 MΩxkm
Conductor Resistance 0.22 mm² : 96 Ω / km – 0.50 mm² : 39 Ω / km
0.75 mm² : 26 Ω / km – 1.00 mm² : 19.50 Ω / km
1.50 mm² : 13.30 Ω / km – 2.50 mm² : 7.98 Ω / km
Test Voltage 0.22 mm² : 1200 V – 0.50 mm² : 1200 V
0.75 mm² : 1200 V – 1.00 mm² : 1200 V
1.50 mm² : 2500 V – 2.50 mm² : 2500 V