APPLICATIONS
These individual and overall screened cables which are not affected by outer signals and parasites are used as signal transmission cables in industrial applications. These used in electronic control systems of computer or audio systems or the communication sector, electronic circuits, measurement devices, machine design, office equipment, etc. Although each core/pair has double screening, These can easily be used in flexible and narrow applications.
| CABLE CONSTRUCTION | |
|---|---|
| Conductor | Stranded Copper Wire Class 5 |
| Insulation | PVC Compound |
| Insulation Color | DIN 47100 Color Coded |
| Stranding | Cores Twisted In Layers |
| Seperator | Pes Tape |
| Stranding | Twisting of Shielded and Sheathed Pairs in Layers |
| Screen | Tinned Copper Wires Braid |
| Outer Sheath | PVC Gray |
| Product Types | LIYCY-CY |
| PACKAGING | 500 – 1000 meters |
| ELECTRICAL PARAMETERS | |
|---|---|
| Working Temperature | – 30 ºC + 70 ºC |
| Bending Radius (min.) | 10 x D |
| Working Voltage | 300 / 500 V |
| Insulation Resistance | >200 MΩxkm |
| Conductor Resistance | 0.22 mm² : 96 Ω/km 0.50 mm² : 39 Ω/km 0.75 mm² : 26 Ω/km 1.00 mm² : 19.50 Ω / km 1.50 mm² : 13.30 Ω / km 2.50 mm² : 7.98 Ω / km |
| Test Voltage | 0.22 mm² : 1200 V 0.50 mm² : 1200 V 0.75 mm² : 1200 V 1.00 mm² : 1200 V 1.50 mm² : 2500 V 2.50 mm² : 2500 V |
| FLAME RETARDANT TEST |
|---|
| IEC 60332-1-2 |
| VDE 0482-332-1-2 |
| EN 60332-1-2 |