APPLICATIONS

These are the cables used in Scada systems, water and natural gas distribution networks, electricity production and distribution, fuel filling facilities, power plants and production lines.

CABLE CONSTRUCTION
ConductorAnnealed Copper Wire 22 AWG
InsulationFoam PE
Insulation ColoursA Wire Green – B Wire Red
FillingPolyvinyl Chloride (PVC) / HFFR
1. ScreenAL-PES Tape
2. ScreenTinned Copper Braiding (Min 85% Closure)
SheathPolyvinyl Chloride (PVC) / HFFR
Sheath ColorRAL 4001 Purple
Packing500 – 1000 mt
INFORMATION TRANSMISSION SPEED
Frequency (MHz)
0.0096
0.0384
4.0
16.0
20.0
Attenuation (dB/100m)
2.5/100m
4.0/100m
22.0/100m
42.0/100m
45.0/100m
Impedance (Ohm)
250 ± 25
185 ± 18
150 ± 15
150 ± 15
150 ± 15
ELECTRICAL PARAMETERS
Max. Operating Voltage125 V
Capacitance30 nF/km
Max. Dc Conductor Resistance57 Ω/km (20˚C)
Min. Insulation Resistance 20°C Min. 5G Ω x km
Nominal Loop Resistance115 Ω/km
Test Tension1000V
Impedance 10MHz20 mΩ/m
Operating Temperature-30°C to 80°C
Min. Bending Radius6 x OD
Maxi. Pulling Tension100 N