APPLICATIONS

These cables are designed for connections of exposed to extreme temperature changes. Often used in iron and steel manufacturing industry, aerospace industry, shipbuilding industry, lighting fixtures, ceramic, glass and cement facto­ries.

CABLE CONSTRUCTION  
Conductior Stranded Annealed Copper Wires (HD 383 Class 5)
Insulation Silicone Compound (HD 22.1 S4 I El2)
Core Identification Color-coded or numbered printed (DIN VDE 0293-308)
Working Temperature -60ºC to +200ºC
Sheath Silicone Compound (HD 22.1 S4 I EM9)
Colour Orange
APPLIED TESTS  
Structural Dimension Tests HD 22.1,2
Mechanical Tests EN 60811-1-1, 1-2, 2-1
Electrical tests HD 22.2
Low Temperature Tests EN 60811-1-4
Fire Performance Tests IEC 61031-1, IEC 60332-1-2, IEC 60754-1-2
Number of Cores x Conductor Cross Section (mm²) Outer Diameter Approx. (mm) Copper Factor (kg/km) Cable Weight (kg/km)
2 x 0.75 6.2 14.4 54.4
3 x 0.75 6.6 21.6 66.0
4 x 0.75 7.6 29.0 86.2
2 x 1 6.6 19.2 63.4
3 x 1 7.4 29.0 84.2
4 x 1 8.0 38.4 101.2
2 x 1.5 7.4 29.0 82.7
3 x 1.5 7.9 43.0 101.8
Number of Cores x Conductor Cross Section (mm²) Outer Diameter Approx. (mm) Copper Factor (kg/km) Cable Weight (kg/km)
4 x 1.5 8.5 58.0 123.5
2 x 2.5 9.1 48.0 127.1
3 x 2.5 9.7 72.0 157.0
4 x 2.5 10.5 96.0 191.0
2 x 4 10.6 77.0 181.3
3 x 4 11.3 115.0 227.5
4x4 12.6 154.0 296.2
FLAME RETARDANT TEST
IEC 60332-1-2
VDE 0482-332-1-2
EN 60332-1-2
SMOKE DENSITY TEST
IEC 61034-2
VDE 0482-1034-2
EN 61034-2
CORROSIVE GAS TEST
IEC 60754-2
VDE 0482-754-2
EN 60754-2